Uploading from the processor – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 205

Advertising
background image

12–2

Uploading and Downloading with A-B Processors

Publication 1770Ć6.5.16 - October 1996

To make sure the program image is stable during an upload,
the PLC interface prohibits program changes during an upload.
When you are using the following procedures, the interface blocks
all access to PLC memory.

To upload information from

See page

PLCĆ2 processors

12-2

PLCĆ3 processors

12-2

PLCĆ5 processors

12-3

SLC 500 processors

12-6

Uploading from a PLCĆ2 Processor

If you have

Then

PLCĆ2/05, Ć2/15, Ć2/16, Ć2/17, or Ć2/30

processor

Make sure the mode selector switch is in

the RUN/PROG or PROG position.

Go to step

2.

PLCĆ2/20 or MiniĆPLCĆ2 processor

The mode selector switch can be in any

position. Go to step

2.

2.

To inhibit programming terminal access, enable the PLC-2
processor to receive mode-setting or physical reads using enter
upload mode.
(For more on enter upload mode, see page

7–10

.)

3.

Upload the information, using one or more physical reads.
(For more on physical read, see page

7–13

.)

4.

To exit the upload mode, use exit download/upload mode.
(For more on exit download/upload mode, see page

7–10

.)

Uploading from a PLCĆ3 Processor

1.

Determine the last memory address used using diagnostic status.
(For more on diagnostic status, see page

7–6

.)

2.

Request the right to upload from the PLC-3 processor using
upload request. (For more on upload request, see page

7–34

.)

3.

Shut down the PLC-3 processor using shutdown request.
(For more on shutdown, see page

7–28

.)

4.

Upload information using one or more physical reads.
(For more on physical read, see page

7–13

.)

5.

Exit the upload mode using restart request. (For more on restart
request,
see page

7–23

.)

Uploading from the

Processor

1.

Advertising