14–3
Line Monitor Examples
Publication 1770Ć6.5.16 - October 1996
In the following example an unprotected read (CMD 01 hex) is sent:
•
from a computer connected to a 1770-KF2 with Data Highway
node address 012 (octal)
•
to the PLC-2/30 connected to a 1771-KA2 with Data Highway
node address 011 (octal)
node 012
DH link
1770ĆKF2
computer
1771ĆKA2
PLCĆ2/30
node 011
Command
Path 1
DLE
STX
DST
SRC
CMD
STS
TNS
ADDR
SIZE
DLE
ETX
BCC
Path 1
10
02
09
00
01
00
01
00
11
00
02
10
03
E2
Path 2
DLE
ACK
Path 2
10
06
Reply (sometime later)
Path 1
DLE
STX
DST
SRC
CMD
STS
TNS
DATA
DLE
ETX
BCC
Path 1
10
02
0A
09
41
00
01
00
FF
FF
10
03
AD
Path 2
DLE
ACK
Path 2
10
06
FullĆduplex PLCĆ2 Line
Monitor Example