Full duplex plc 2 line monitor example, Fullćduplex plcć2 line monitor example, Command – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 235: Reply (sometime later)

Advertising
background image

14–3

Line Monitor Examples

Publication 1770Ć6.5.16 - October 1996

In the following example an unprotected read (CMD 01 hex) is sent:

from a computer connected to a 1770-KF2 with Data Highway
node address 012 (octal)

to the PLC-2/30 connected to a 1771-KA2 with Data Highway
node address 011 (octal)

node 012

DH link

1770ĆKF2

computer

1771ĆKA2

PLCĆ2/30

node 011

Command

Path 1

DLE

STX

DST

SRC

CMD

STS

TNS

ADDR

SIZE

DLE

ETX

BCC

Path 1

10

02

09

00

01

00

01

00

11

00

02

10

03

E2

Path 2

DLE

ACK

Path 2

10

06

Reply (sometime later)

Path 1

DLE

STX

DST

SRC

CMD

STS

TNS

DATA

DLE

ETX

BCC

Path 1

10

02

0A

09

41

00

01

00

FF

FF

10

03

AD

Path 2

DLE

ACK

Path 2

10

06

FullĆduplex PLCĆ2 Line

Monitor Example