8–10

Message Packet Status Codes (STS, EXT STS)

Publication 1770Ć6.5.16 - October 1996

Command

Explanation

STS Code

EXT STS Code

PLCĆ3 bit write

-

10

More than four bytes of data exist after the PLCĆ3

address in the command message.

-

30

The local PLCĆ3 interface module has executed a

shutdown request.

-

40

A backplane error (memory parity, timeout, or

disconnect) has occurred.

-

60

The keyswitch setting does not allow access to file.

-

70

The local PLCĆ3 in the Program mode.

1

F0

There was an error in converting the block address

(major section > 63, context > 15, section > 15).

2

F0

Three or fewer addressing levels specified for a

PLCĆ3 word address.

3

F0

Conversion of a file address to a block address

resulted in more than 9 addressing levels.

4

F0

The symbolic address was not found.

5

F0

The symbolic address is zero or more than eight

bytes.

6

F0

File not found.

The DST address does not specify a PLCĆ3 word.

The PLCĆ3 address specifies more levels than

required.

The word specified by the PLCĆ3 address does not

exist.

9

F0

The file is larger than 65,535 words.

B

F0

The remote node does not have access to the DST

file.