Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 137

8–10
Message Packet Status Codes (STS, EXT STS)
Publication 1770Ć6.5.16 - October 1996
Command
Explanation
STS Code
EXT STS Code
PLCĆ3 bit write
-
10
More than four bytes of data exist after the PLCĆ3
address in the command message.
-
30
The local PLCĆ3 interface module has executed a
shutdown request.
-
40
A backplane error (memory parity, timeout, or
disconnect) has occurred.
-
60
The keyswitch setting does not allow access to file.
-
70
The local PLCĆ3 in the Program mode.
1
F0
There was an error in converting the block address
(major section > 63, context > 15, section > 15).
2
F0
Three or fewer addressing levels specified for a
PLCĆ3 word address.
3
F0
Conversion of a file address to a block address
resulted in more than 9 addressing levels.
4
F0
The symbolic address was not found.
5
F0
The symbolic address is zero or more than eight
bytes.
6
F0
•
File not found.
•
The DST address does not specify a PLCĆ3 word.
•
The PLCĆ3 address specifies more levels than
required.
•
The word specified by the PLCĆ3 address does not
exist.
9
F0
The file is larger than 65,535 words.
B
F0
The remote node does not have access to the DST
file.