10–3

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

1747ĆL20, ĆL30, ĆL40, ĆL511, ĆL514, ĆL524 (SLC 500, SLC 5/01 and

SLC 5/02 processors) Status Bytes

Bytes

Bits

Contents

Description

1

0Ć7

mode/status

00

2

0Ć7

type extender

EE

3

0Ć7

extended interface type

1F

4

0Ć7

extended processor type

1A = 20, 30, & 40 I/O SLC fixed controllers

18 = 1747ĆL511, ĆL514 SLC 5/01 controller

25 = 1747ĆL524 and SLC 5/02 controller

5

0Ć4

series/revision

= 0 (firmware release1)

= 1 (firmware release 2), etc.

5Ć7

= 0 (series A)

= 1 (series B), etc.

6 - 16

all

bulletin number/name

(in ASCII)

500 - 20 = 1747ĆL20 (SLC 500 fixed controller)

500 - 30 = 1747ĆL30 (SLC 500 fixed controller)

500 - 40 = 1747ĆL40 (SLC 500 fixed controller)

5/01 = 1747ĆL511 & ĆL514

5/02 = 1747ĆL524

ProductĆspecific Information
17

all

major error word

low byte

18

all

major error word

high byte

19

0Ć4

processor mode

status/control word

0 = download

1 = program

2 = reserved

3 = idle due to SUS instruction

4 = reserved

5 = reserved

6 = run

7 = test continuous scan

8 = test single scan 9Ć31 = reserved

5

forces active

6

forces installed

7

communication active

20

0

processor mode status/control word

protection power loss

20

1

processor mode status/control word

(high byte)

startup protect fault

2

( g y )

load memory module on error

3

load memory module always

4

load memory module and run

5

major error Ć processor halted

6

locked

7

first pass bit

21

0Ć7

program ID

low byte

22

0Ć7

program ID

high byte

23

0Ć7

processor RAM size (in Kbytes)

24

0

directory file corrupted

1

not used

= 0

2Ć7

program owner node address

= 00 - 1F: program owner node address

= 3F: no program owner

SLC 5/02 processors only.