Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 174

10–3
Diagnostic Status Information
Publication 1770Ć6.5.16 - October 1996
1747ĆL20, ĆL30, ĆL40, ĆL511, ĆL514, ĆL524 (SLC 500, SLC 5/01 and
SLC 5/02 processors) Status Bytes
Bytes
Bits
Contents
Description
1
0Ć7
mode/status
00
2
0Ć7
type extender
EE
3
0Ć7
extended interface type
1F
4
0Ć7
extended processor type
1A = 20, 30, & 40 I/O SLC fixed controllers
18 = 1747ĆL511, ĆL514 SLC 5/01 controller
25 = 1747ĆL524 and SLC 5/02 controller
5
0Ć4
series/revision
= 0 (firmware release1)
= 1 (firmware release 2), etc.
5Ć7
= 0 (series A)
= 1 (series B), etc.
6 - 16
all
bulletin number/name
(in ASCII)
500 - 20 = 1747ĆL20 (SLC 500 fixed controller)
500 - 30 = 1747ĆL30 (SLC 500 fixed controller)
500 - 40 = 1747ĆL40 (SLC 500 fixed controller)
5/01 = 1747ĆL511 & ĆL514
5/02 = 1747ĆL524
ProductĆspecific Information
17
all
major error word
low byte
18
all
major error word
high byte
19
0Ć4
processor mode
status/control word
0 = download
1 = program
2 = reserved
3 = idle due to SUS instruction
4 = reserved
5 = reserved
6 = run
7 = test continuous scan
8 = test single scan 9Ć31 = reserved
5
forces active
6
forces installed
7
communication active
20
0
processor mode status/control word
protection power loss
20
1
processor mode status/control word
(high byte)
startup protect fault
➀
2
( g y )
load memory module on error
3
load memory module always
➀
4
load memory module and run
➀
5
major error Ć processor halted
6
locked
➀
7
first pass bit
➀
21
0Ć7
program ID
low byte
22
0Ć7
program ID
high byte
23
0Ć7
processor RAM size (in Kbytes)
24
0
directory file corrupted
1
not used
= 0
2Ć7
program owner node address
= 00 - 1F: program owner node address
= 3F: no program owner
➀
SLC 5/02 processors only.