8–7
Message Packet Status Codes (STS, EXT STS)
Publication 1770Ć6.5.16 - October 1996
Command
Explanation
STS Code
EXT STS Code
PLC/PLCĆ2 read
-
10
•
The required twoĆbyte ADDR field and oneĆbyte
SIZE field are missing in the command message.
•
The ADDR value is odd (that is, it does not specify
a word address).
•
The value of SIZE is 0.
•
The value of SIZE is greater than 244.
•
The SIZE value specifies an odd number of bytes.
-
30
The local PLCĆ3 interface module has executed a
shutdown request to the local PLCĆ3 processor.
-
40
Local PLCĆ3 backplane error (either memory parity,
timeout, or disconnect).
-
50
•
A destination (DST) file does not exist.
•
The DST file is too small.
•
The source (SRC) file is more than 65,535 words
long.
-
70
PLCĆ3 processor is in Program mode.
PLC/PLCĆ2 bit write
-
10
Incomplete bit description because the number of
bytes after the TNS word is not a multiple of 4.
-
30
The local PLCĆ3 interface module has executed a
shutdown request to the local PLCĆ3 processor.
-
40
Local PLCĆ3 backplane error (either memory parity
or timeout/disconnect).
-
50
•
A DST file does not exist.
•
The DST bits do not exist in the destination file.
•
Length of the SRC file is greater than 65,535
words.
-
60
The keyswitch setting at local PLCĆ3 processor
prohibits access.
-
70
The local PLCĆ3 processor is in Program mode.