Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 134

Advertising
background image

8–7

Message Packet Status Codes (STS, EXT STS)

Publication 1770Ć6.5.16 - October 1996

Command

Explanation

STS Code

EXT STS Code

PLC/PLCĆ2 read

-

10

The required twoĆbyte ADDR field and oneĆbyte

SIZE field are missing in the command message.

The ADDR value is odd (that is, it does not specify

a word address).

The value of SIZE is 0.

The value of SIZE is greater than 244.

The SIZE value specifies an odd number of bytes.

-

30

The local PLCĆ3 interface module has executed a

shutdown request to the local PLCĆ3 processor.

-

40

Local PLCĆ3 backplane error (either memory parity,

timeout, or disconnect).

-

50

A destination (DST) file does not exist.

The DST file is too small.

The source (SRC) file is more than 65,535 words

long.

-

70

PLCĆ3 processor is in Program mode.

PLC/PLCĆ2 bit write

-

10

Incomplete bit description because the number of

bytes after the TNS word is not a multiple of 4.

-

30

The local PLCĆ3 interface module has executed a

shutdown request to the local PLCĆ3 processor.

-

40

Local PLCĆ3 backplane error (either memory parity

or timeout/disconnect).

-

50

A DST file does not exist.

The DST bits do not exist in the destination file.

Length of the SRC file is greater than 65,535

words.

-

60

The keyswitch setting at local PLCĆ3 processor

prohibits access.

-

70

The local PLCĆ3 processor is in Program mode.