Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 213

Advertising
background image

12–10

Uploading and Downloading with A-B Processors

Publication 1770Ć6.5.16 - October 1996

Procedure 2

1.

Verify the processor type using diagnostic status. (For more on
diagnostic status, see page

7–6

.)

2.

Place the PLC-5 processor in Program or Remote
program mode using set CPU mode or the keyswitch on the front
of the processor. (For more on set CPU mode,
see page

7–26

.)

3.

Place the PLC-5 processor in Download mode using download all
request.
(For more on download all request, see page

7–7

.)

4.

Send PLC-5 memory information to the appropriate physical
addresses in PLC-5 memory using write bytes physical with the
information stored in the archive file from the upload procedure.
(For more on write bytes physical, see page

7–35

.)

5.

Exit Download mode using download complete. (For more on
download complete, see page

7–7

.)

Downloading to an SLC 500 Processor

If you have this SLC processor

Then

SLC 500, SLC 5/01, or SLC 5/02

Follow procedure 1 on page

12-11

SLC 5/03 or SLC 5/04

Follow procedure 2 on page

12-12