Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 184

Advertising
background image

10–13

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

1775ĆKA, ĆS5 and ĆSR5 Status Bytes

Bytes

Bits

Contents

Description

1

0 - 1

Operating status of

PLCĆ3 processor

0 = Program mode

1 = Test mode

2 = Run mode

2

Not used

3

0 = Normal

1 = Major processor fault

4

0 = Normal

1 = Shutdown request

5

0 = Normal

1 = Shutdown in effect

6 - 7

Not used

2

0 - 3

Type of node interface

and processor

6 = 1775ĆKA - Data Highway port, 1775ĆS5, or 1775ĆSR5

7 = 1775ĆKA - RSĆ232ĆC port

4 - 7

and processor

7 = 1775ĆKA - RSĆ232ĆC port

12 = 1775ĆS5,ĆSR5 (new revisions only)

3

all

Current context

(stored in bits 4 to 7)

4

all

Thumbwheel number

5 - 6

all

Mode control word

The logical address of the mode control word is E0.0.0.8.

7 - 8

all

Starting byte address of diagnostic

counters and timers

There is a separate block of diagnostic timers and counters

for the DH port and the RSĆ232 port. The address given here

is for the port that received the diagnostic status command.

9

0 - 4

Series and revision number of

0 = Revision A

the module

1 = Revision B, etc.

5 - 7

The 1775ĆS5 and 1775ĆSR5 (series A)

appear as series C modules.

0 = Series A

1 = Series B, etc.

10

all

Not used

Not used

11 - 14 all

The physical address of the unused

word of PLCĆ3 system memory.

The physical address corresponding to the logical address

E60.0.0.0. This is the last word to read or write in an upload

or download.

15 - 18 all

The total number of words in the PLCĆ3

system memory (both used and unused)

Advertising