1773, 1775, and 1779 cat. nos, 1773ćka status bytes – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 182

Advertising
background image

10–11

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

For status information from these cat. nos.

See page

1773ĆKA

10-11

1775ĆKA, 1775ĆS5, and 1775ĆSR5

10-13

1779ĆKP5

10-14

1773ĆKA Status Bytes

Bytes

Bits

Contents

Description

1

0

Operating status of

= 1 if controller #1 is active

1

p

g

controllers on loop

= 1 if controller #2 is active

2

= 1 if controller #3 is active

3

= 1 if controller #4 is active

4

= 1 if controller #5 is active

5

= 1 if controller #6 is active

6

= 1 if controller #7 is active

7

= 1 if controller #8 is active

2

0 - 3

Node interface and

processor type

8 = 1773ĆKA, DH port

9 = 1773ĆKA, RSĆ232ĆC port

12 = 1775ĆS5,ĆSR5 (new revisions only)

4 - 7

8 = PLCĆ4 Microtrol processor

3 - 4

0

DH port options

0 = 57,600 bits per second DH baud rate

1 = Undefined

1

Not used

2

0 = Privileged commands enabled

1 = Privileged commands disabled

3

0 = Unprotected commands enabled

1 = Unprotected commands disabled

4

0 = Protected commands enabled

1 = Protected commands disabled

5 - 7

Not used

8 - 15

Octal node number

5 Ć 6

0

RSĆ232ĆC port options

0 = Even parity; 1 = No parity

1 - 3

p

p

Baud rate

0 = 19,200 bps

1 = 8,600 bps

2 = 4,800 bps

3 = 2,400 bps

4 = 1,200 bps

5 = 600 bps

6 = 300 bps

7 = 110 bps

4 - 10

Not used

11

0 = Protected commands enabled

1 = Protected commands disabled

12

0 = Embedded responses enabled

1 = Embedded responses disabled

13

0 = Unprotected commands enabled

1 = Unprotected commands disabled

14

0 = Privileged commands enabled

1 = Privileged commands disabled

15

0 = HalfĆduplex protocol

1 = FullĆduplex protocol

7 - 8

Starting byte address of diagnostic

timers and counters

1773, 1775, and 1779

Cat. Nos.