Application Layer Message Packets

Publication 1770Ć6.5.16 - October 1996

DST and SRC

Form the DST and SRC bytes of a reply message by interchanging
the DST and SRC bytes of the corresponding command message:

DST

SRC

SRC

DST

Command

Reply

Byte

Contents

Value supplied by Value range

DST

(destination)

receiving message application layer

0 to 376 (octal) for DF1

0 to 376 (octal) for DH

SRC

(source)

sending message

data link layer

0 to 376 (octal) for DH

0 to 77 (octal) for DH+

0 to 31 (decimal ) for DH485

When sending messages from asynchronous devices, special
consideration must be given to the SRC byte:

When sending a message from an

asynchronous device connected

Set the SRC byte

to the network

= 0 (the module will set the byte to its own

node number)

directly to a 1771ĆKG

 10 (octal)

If you connect to channel 0 of a PLCĆ5/11, Ć5/20, Ć5/30, Ć5/40, Ć5/60 or Ć5/80 processor and you
send a PLCĆ2 unprotected write, protected write, protected bit write, or unprotected bit write, what
you put into the SRC byte is very important. This determines the compatibility file. This means
that the value of the SRC byte specifies the data table file number that is written to the PLCĆ5
processor. The source byte will not be overwritten by channel 0. For SLC 500 processors, the
compatibility file is always 9.