2–8
Understanding DF1 Protocol
Publication 1770Ć6.5.16 - October 1996
Table 2.D
FullĆduplex Transmission Symbols
Symbol
Type
Meaning
DLE STX
control symbol
Sender symbol that indicates the start of a message
frame.
DLE ETX
BCC/CRC
control symbol
Sender symbol that terminates a message frame.
DLE ACK
control symbol
Response symbol which signals that a message
frame has been successfully received.
DLE NAK
control symbol
Response symbol which signals that a message
frame was not received successfully.
DLE ENQ
control symbol
Sender symbol that requests retransmission of a
response symbol from the receiver.
APP DATA
data symbol
Single character data values between 00Ć0F and
11ĆFF. Includes data from application layer including
user programs and common application routines.
A data 10
16
is sent as 10 10 (DLE DLE).
DLE DLE
data symbol
Represents the data value of 10
16
.