Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 180

Advertising
background image

10–9

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

Bytes

Bits

Contents

Description
1771ĆKG Module (Series B)

1

0 = second module; 1 = first module

2

0 = accept physical/unprotected reads and writes disabled

1 = accept physical/unprotected reads and writes enabled

4, 3, 0

Binary values:

Value

Parity

Error

Embedded

Protocol

Check

Responses

000

none

BCC

disabled

fullĆduplex

100

even

BCC

disabled

fullĆduplex

010

none

BCC

enabled

fullĆduplex

110

even

BCC

enabled

fullĆduplex

001

none

BCC

disabled

halfĆduple

x

101

even

BCC

disabled

halfĆduple

x

011

none

CRC

enabled

fullĆduplex

111

none

CRC

disabled

halfĆduple

x

5 - 7

Asynchronous link baud rate:

0 = 110 bps

1 = 300 bps 2 = 600 bps

3 = 1200 bps 4 = 2400 bps 5 = 4800 bps

6 = 9600 bps 7 = 19200 bps

Advertising