Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 180
Advertising
10–9
Diagnostic Status Information
Publication 1770Ć6.5.16 - October 1996
Bytes
Bits
Contents
Description
1771ĆKG Module (Series B)
1
0 = second module; 1 = first module
2
0 = accept physical/unprotected reads and writes disabled
1 = accept physical/unprotected reads and writes enabled
4, 3, 0
Binary values:
Value
Parity
Error
Embedded
Protocol
Check
Responses
000
none
BCC
disabled
fullĆduplex
100
even
BCC
disabled
fullĆduplex
010
none
BCC
enabled
fullĆduplex
110
even
BCC
enabled
fullĆduplex
001
none
BCC
disabled
halfĆduple
x
101
even
BCC
disabled
halfĆduple
x
011
none
CRC
enabled
fullĆduplex
111
none
CRC
disabled
halfĆduple
x
5 - 7
Asynchronous link baud rate:
0 = 110 bps
1 = 300 bps 2 = 600 bps
3 = 1200 bps 4 = 2400 bps 5 = 4800 bps
6 = 9600 bps 7 = 19200 bps
Advertising