Unprotected write – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 119

Advertising
background image

7–32

Communication Commands

Publication 1770Ć6.5.16 - October 1996

unprotected write

1774-PLC, PLC-2, PLC-3, PLC-5
Writes words of data into any area of PLC and PLC-2 data table
memory. In PLC-3 and PLC-5 processors, the data is written into the
PLC-2 compatibility file.

C

CMD

08

STS

TNS

ADDR

R

STS

TNS

CMD

48

Data (max. 244 bytes)

DST SRC

SRC DST

SLC 500, MicroLogix 1000
Writes data to a common interface file (CIF). The SLC CIF is data
file number 9; the MicroLogix CIF is integer file 7.

CMD

08

STS

TNS

CMD

48

STS

TNS

DST SRC

SRC DST

Address

C

R

Low High

Address - Logical offset into the CIF. Value is in words or bytes as shown below:

SLC 500, SLC 5/01 and SLC 5/02 (SLC 5/02 prior to series C FRN 3) processors use word addressing

SLC 5/02 series C FRN 3 and later, SLC 5/03, and SLC 5/04 processors select word or byte addressing

for S:2/8 = 0 (default) Ċ word addressing is used

for S:2/8 = 1 Ċ byte addressing is used

Data - Data to be written. This size of the data is implied by the number of data bytes sent.

for SLC 500, SLC 5/01 and SLC 5/02 processors: valid range is 0 Ć 94 bytes (odd or even)

for SLC 5/03 and 5/04 processors - with internet protocol: valid range is 0 Ć 223 bytes (odd or even)

without internet protocol: valid range is 0 Ć 234 bytes (odd or even)

Data (size implied by

data sent)

1774ĆPLC

PLCĆ2

PLCĆ3

PLCĆ5

SLC 500

MicroLogix 1000