Ext sts byte, Remote sts error codes – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 130

8–3
Message Packet Status Codes (STS, EXT STS)
Publication 1770Ć6.5.16 - October 1996
Remote STS Error Codes
The remote STS error code nibble contains errors found by the
remote node receiving the command. Error codes (in hex) that you
may find in the remote error code nibble of the STS byte include:
Code
Explanation
00
SuccessĊno error
10
Illegal command or format
20
Host has a problem and will not communicate
30
Remote node host is missing, disconnected, or shut down
40
Host could not complete function due to hardware fault
50
Addressing problem or memory protect rungs
60
Function not allowed due to command protection selection
70
Processor is in Program mode
80
Compatibility mode file missing or communication zone problem
90
Remote node cannot buffer command
A0
Wait ACK (1775ĆKA buffer full)
B0
Remote node problem due to download
C0
Wait ACK (1775ĆKA buffer full)
D0
Not used
E0
Not used
F0
Error code in the EXT STS byte
You have an EXT STS byte if your STS code is F0 (hex).
Definitions for this byte vary, depending on the command code
(or type of command) in your message packet:
CMD code (hex)
Type of code in EXT STS byte
Refer to
00 to 08
No EXT STS byte
not applicable
0F
DH/DH+ codes
0B, 1A, or 1B
DH485 codes
EXT STS Byte