Ext sts byte, Remote sts error codes – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 130

Advertising
background image

8–3

Message Packet Status Codes (STS, EXT STS)

Publication 1770Ć6.5.16 - October 1996

Remote STS Error Codes

The remote STS error code nibble contains errors found by the
remote node receiving the command. Error codes (in hex) that you
may find in the remote error code nibble of the STS byte include:

Code

Explanation

00

SuccessĊno error

10

Illegal command or format

20

Host has a problem and will not communicate

30

Remote node host is missing, disconnected, or shut down

40

Host could not complete function due to hardware fault

50

Addressing problem or memory protect rungs

60

Function not allowed due to command protection selection

70

Processor is in Program mode

80

Compatibility mode file missing or communication zone problem

90

Remote node cannot buffer command

A0

Wait ACK (1775ĆKA buffer full)

B0

Remote node problem due to download

C0

Wait ACK (1775ĆKA buffer full)

D0

Not used

E0

Not used

F0

Error code in the EXT STS byte

You have an EXT STS byte if your STS code is F0 (hex).
Definitions for this byte vary, depending on the command code
(or type of command) in your message packet:

CMD code (hex)

Type of code in EXT STS byte

Refer to

00 to 08

No EXT STS byte

not applicable

0F

DH/DH+ codes

page

8-4

0B, 1A, or 1B

DH485 codes

page

8-5

EXT STS Byte

Advertising