10–23

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

Bytes

Description

Contents

Bits

19

all

Debug mode

= 0, OFF

0 0, ON

20 - 21 all

Hold point file

used if Debug mode is ON. Low byte first.

22 - 23 all

Hold point element

used if Debug mode is ON. Low byte first.

24 - 25 all

Edit time stamp seconds

Low byte first.

26 - 27 all

Edit time stamp minute

Low byte first.

28 - 29 all

Edit time stamp hour

Low byte first

30 - 31 all

Edit time stamp day

Low byte first

32 - 33 all

Edit time stamp month

Low byte first

34 - 35 all

Edit time stamp year

Low byte first

36

all

Port number this command received on

For status information from these cat. nos.

See page

5130ĆRM1, ĆRM2 (PLCĆ5/250) controllers

10-23

5130ĆRM1,ĆRM2 (PLCĆ5/250) Status Bytes

Bytes

Bits

Contents

Description

1

0 - 2

Operating status of

PLCĆ5/250 processor

0 = Program load

1 = Not used

2 = Run mode

3 = Not used

4 = Remote program load

5 = Remote test

6 = Remote run

7 = Not used

3

0 = Normal

1 = Major processor fault

4

0 = Normal

1 = Download mode

5

0 = Normal

1 = OffĆline

6

0 = Not testing edits

1 = Testing edits

7

0 = No edits in processor

1 = Edits in processor

2

0 - 3

Processor Type

0E = expansion byte

4 - 7

yp

D0 = PLCĆ5/250

3

all

ID

4

0

Forces active if 1

1

Backup system active if 1

2

Partner system active if 1

3

Edit resource allocated if 1

4

Outputs reset if 1

5

Memory invalid if 1

6

SFC forces active if 1

7

Edit resource allocated by user if 1

5

all

Processor Station Address on Link

5130 Cat. Nos.