Protected write, Read bytes physical (physical read), Read diagnostic counters – Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 106

Advertising
background image

7–19

Communication Commands

Publication 1770Ć6.5.16 - October 1996

protected write

Writes words of data into limited areas of the PLC data table
memory. Its access is limited by memory access rungs in the
communication zone of the processor’s ladder diagram program.

C

CMD

00 STS

TNS

ADDR

R

STS

TNS

CMD

40

Data (max. 244 bytes)

DST SRC

SRC DST

read bytes physical (physical read)

Performs an upload after receiving a reply that an upload (download)
all request
has been successfully performed.

CMD

0F

STS

FNC

17

TNS

C

CMD

4F STS

TNS

R

TNS

DST SRC

SRC DST

A

PLCĆ5 phys. address

Size

Data (up to 240 bytes)

A - extended status byte if there is an error. Otherwise, it will be data at physical address,

first word, low byte.

Size - the number of bytes to read, up to 240 (must be an even number).

read diagnostic counters

Reads up to 244 bytes of data from the PROM or RAM of an
interface module. Use this command to read a module’s diagnostic
timers and counters.

You must use diagnostic status to obtain the starting address of the
diagnostic counters, except for the PLC-5, PLC-5/250, and SLC 500
processors. PLC-5 and PLC-5/250 processors don’t require that this
address be specified, though you must include a dummy value in the
ADDR field, which the PLC-5 or PLC-5/250 processor ignores.
For SLC 500 processors, zero is the only valid value for the ADDR
field. (For listings of read diagnostic counters status information,
see Chapter 10, “Diagnostic Status Information.”)

C

CMD

06

STS

FNC

01

TNS

ADDR

SIZE

R

STS

TNS

CMD

46

Data (max. 244 bytes)

DST SRC

SRC DST

1774ĆPLC

PLCĆ2

PLCĆ3

PLCĆ5

PLCĆ5/250

PLCĆ5

PLCĆ5/250

(receive only)

PLCĆ5/VME

1774ĆPLC

MicroLogix 1000

PLCĆ2

PLCĆ3

PLCĆ5

PLCĆ5/250

(receive only)

SLC 500

SLC 5/03

SLC 5/04