Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual
Page 189

10–18
Diagnostic Status Information
Publication 1770Ć6.5.16 - October 1996
Bytes
Description
Contents
Bits
3 - 4
all
Octal address of the start of the
PLC program
5 - 6
all
0 = not used
7 - 8
all
Starting byte address of diagnostic
counters and timers.
Starting byte address of diagnostic counters and timers.
9
0 - 4
Series and revision level of interface
module.
0 = Revision A
1 = Revision B, etc.
5 - 7
0 = Series A
1 = Series B, etc.
10
0 - 1
Settings of the option switches on the
0 = Undefined
1 = Undefined
g
p
node interface module
2 = Undefined
3 = not used
2
0 = PLCĆ2 processor
1 = All other PLCĆ2 Family processors
3
0 = Protected commands disabled
1 = Protected commands enabled
4
0 = Unprotected commands disabled
1 = Unprotected commands enabled
5
Not used
6
0 = Physical writes disabled
1 = Physical writes enabled
7
0 = Transmission unprotected commands disabled
1 = Transmission unprotected commands enabled
11
0
0 = No terminal directly connected
1 = Terminal directly connected
1
0 = No terminal is editing over DH+ link
1 = A terminal is editing over DH+ link
2
0 = Directly connected terminal is not editing
1 = Directly connected terminal is editing
3 - 7
Not used
will be set to zeros
12
0 - 2
Indicates the number of I/O racks the
3
PLCĆ2 is configured for.
0 = No I/O points are currently forced on or off.
1 = An I/O point has been forced on or off since the last
time the directly connected terminal was connected.
Important: This bit is set until the directly connected
terminal is disconnected or returns to the mode select"
screen, even if the forces have subsequently been
removed.