Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 179

Advertising
background image

10–8

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

Bytes

Description

Contents

Bits

9

0 - 4

Series and revision level of

interface module.

1770ĆKF2/A identifies itself as Series D"

in byte 9, bits 5 to 7. Series B 1770ĆKF2

0 = Revision A

1 = Revision B, etc.

5 - 7

y

,

identifies itself as Series E, and so on.

1771ĆKA identifies itself as a Series A.

1771ĆKA2 Series A identifies itself as a

Series B, and so on.

0 = Series A

1 = Series B, etc.

10121

0Ć7

Settings of the option switches on the

node interface module.

This byte is not used in replies by 1771ĆKC/KD or ĆKE/KF

modules.

For the other modules, the bits of this byte are defined as

follows.
1771ĆKA and 1771ĆKA2 modules
1771ĆKA2 status information is opposite of 1771ĆKA, as

noted.

0 - 1

0 = 57,600 bits per second baud rate for DH link (undefined

for 1771ĆKA2)

1 = Undefined

2 = Undefined

3 = Undefined (57,600 for 1771ĆKA2)

2

0 = All other PLCĆ2 Family processors (PLCĆ2 processor for

1771ĆKA2)

1 = PLCĆ2 processor (all other PLCĆ2 processors for

1771ĆKA2)

3

0 = Protected commands enabled (disabled for 1771ĆKA2)

1 = Protected commands disabled (enabled for 1771ĆKA2)

4

0 = Unprotected commands enabled (disabled for 1771ĆKA2)

1 = Unprotected commands disabled (enabled for 1771ĆKA2)

5

not used

6

0 = Physical writes enabled (disabled for 1771ĆKA2)

1 = Physical writes disabled (enabled for 1771ĆKA2)

7

0 = Transmission unprotected commands enabled (disabled

for 1771ĆKA2)

1 = Transmission unprotected commands disabled (enabled

for 1771ĆKA2)
1771ĆKG Module (Series A)

0

0 = FullĆduplex protocol; 1 = HalfĆduplex protocol

1

0 = Physical writes disabled; 1 = Physical writes enabled

2

0 = Unprotected commands disabled; 1 = Unprotected

commands enabled

3

0 = Embedded responses disabled; 1 = Embedded

responses enabled

4

0 = No parity; 1 = Even parity

5 - 7

Asynchronous link baud rate

0 = 110 bps

1 = 300 bps

2 = 600 bps

3 = 1200 bps

4 = 2400 bps

5 = 4800 bps

6 = 9600 bps

7 = 19200 bps

Advertising