10–21

Diagnostic Status Information

Publication 1770Ć6.5.16 - October 1996

1785ĆLT3 (PLCĆ5/12) and 1785ĆLT2 (PLCĆ5/25) Status Bytes

Bytes

Bits

Contents

Description

1

0 - 2

Operating status of PLCĆ5 processor

0 = Program load

1 = Not used

2 = Run mode

3 = Not used

4 = Remote program load

5 = Remote test

6 = Remote run

7 = Not used

3

0 = Normal

1 = Major processor fault

4

0 = Normal

1 = Download mode

5

Not used

6

0 = Not testing edits

1 = Testing edits

7

0 = Not testing edits

1 = Testing edits

2

0 - 3

Processor Type

B = PLCĆ5

4 - 7

yp

E = Expansion byte

3

Processor Expansion Byte

13 = 1785ĆLT3 (PLCĆ5/12)

14 = 1785ĆLT2 (PLCĆ5/25)

4 - 7

Size of user memory

low word first, low byte first

8

0 - 4

Series and revision of the PLCĆ5

0 = Revision A

1 = Revision B, etc.

5 - 7

0 = Series A

1 = Series B, etc.

9

all

Processor number on DH+ Link

10

all

all I/O address

Address of the processor if it is an adapter. If it is a scanner,

value is 0FDH.

11

0

I/O and communication parameters

0 = Double density

1

p

1 = Adapter mode

2

1 = Module group 4 top half

5

1 = Adapter is half rack

6

1 = Data Highway Plus at 115K baud

12 - 13 all

Number of data table files

low byte first

14 - 15 all

Number of data type files

low byte first

16

0

Forcing status

1 = Forces active

4

1 = Forces are present in the tables.

1 = Forces are present in the tables.

17

all

Memory protect indication

nonĆzero means memory is protected

18

all

Bad RAM indication

nonĆzero means RAM is bad, must be cleared