Rockwell Automation 1770, D17706.5.16 Ref Mnl DF1 Protocol Command User Manual

Page 105

Advertising
background image

7–18

Communication Commands

Publication 1770Ć6.5.16 - October 1996

protected typed logical write with three address fields

Writes data to a logical address in a SLC processor.

CMD

0F

STS

FNC

AA

TNS

DST SRC

Ele.

No.

File

Type

C

Byte

Size

File

No.

S/Ele.

No.

DATA

CMD

4F STS

SRC DST

R

EXT

STS

The EXT STS field is only included if there is an error.

TNS

Field

Description

Byte Size

The size of data to be read (in bytes), not including the address fields

or other overhead bytes.

File Number

Addresses files 0Ć254 only. For higher addresses, setting this byte to

FF expands this field to three bytes total. Use the second and third

bytes for the expanded file address (low address byte first).

File Type

Use one of the these values for this field. Do not use any other

values; doing so may result in unpredictable results.

80Ć83 hex: reserved

84 hex: status

85 hex: bit

86 hex: timer

87 hex: counter

88 hex: control

89 hex: integer

8A hex: floating point

8D hex: string

8E hex: ASCII

Element Number

Addresses elements 0Ć254 only. For higher addresses, setting this

byte to FF expands this field to three bytes. Use the second and third

bytes for the expanded element address (low address byte first).

SubĆelement

Number

Addresses subĆelements 0Ć254 only. For higher addresses, setting

this byte to FF expands this field to three bytes. Use the second and

third bytes for the expanded subĆelement address (low address byte

first).

DATA

For SLC 5/01 or SLC 5/02

= 82 bytes (41 words)

For SLC 5/03 or 5/04

= 223 bytes with IP (does not apply to DF1 drivers)

= 234 bytes without IP (applies to DF1 drivers)

SLC 500

SLC 5/03

SLC 5/04

Advertising