Configuration diagnostics, Post configuration diagnostics, Non-critical versus critical module errors – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 113: Non-critical errors, Critical errors, Non-critical errors critical errors

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

113

Diagnostics and Troubleshooting

Chapter 5

Configuration Diagnostics

When a configuration is sent, the module performs a diagnostic check to see that
the configuration is valid. This results in either a valid ModConfig bit or module
configuration error. See the

Configuration Error Codes table on page 117

for

configuration error codes.

Post Configuration Diagnostics

If the ModConfig bit in the input array is set, then the module has accepted the
configuration. Now, on every scan, each channel status flag in the input array is
examined. The output array is checked on each scan for compatibility with the
configuration array.

Non-critical versus
Critical Module Errors

The 1769-HSC module has non-critical and critical errors.

Non-critical Errors

Non-critical module errors are typically recoverable. Non-critical error
conditions are indicated by the extended error code. See the

Configuration Error

Codes table on page 117

for more information.

Critical Errors

Critical module errors are conditions that prevent normal or recoverable
operation of the system. When these types of errors occur, the system typically
leaves the Run or Program mode and enters the fault mode of operation until the
error can be dealt with. Critical module errors are indicated in the

General

Common Hardware Error Codes table on page 116

.

TIP

The OK status indicator will be in a flashing red state for all of the error
codes in the

Configuration Error Codes table on page 117

.