Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

25

Module Operation

Chapter 2

X1 Quadrature Encoder Mode Selection

In this mode, when a quadrature encoder is attached to inputs A and B, the count
direction is determined by the phase relation of inputs A and B. If A leads B, the
counter increments. If B leads A, the counter decrements. In other words, when B
is low, the count increments on the rising edge of input A and decrements on the
falling edge of input A. If B is high, all rising transitions on input A are ignored.
The counter changes value only on one edge of input A as shown in Figure 5.

For more information see

Direction Inhibit and Direction Invert Output

Control Bits on page 21

and their effect on Quadrature signals on

page 27

.

Table 5 - Up and Down Counting

Direction
Inhibit Bit

Direction
Invert Bit

Input A (count)

Input B (direction)

Change in
Count Value

0

0

0, 1,

1

0, 1,

-1

0

0

1

0, 1,

-1

0, 1,

1

0

1

0

0, 1,

1

0, 1,

1

0

1

1

0, 1,

-1

0, 1,

-1

0

TIP

When both A and B transition at the same time, instead of in the defined
90° phase separation, the quadrature signal is invalid.