Module Operation
Chapter 2
X1 Quadrature Encoder Mode Selection
In this mode, when a quadrature encoder is attached to inputs A and B, the count
direction is determined by the phase relation of inputs A and B. If A leads B, the
counter increments. If B leads A, the counter decrements. In other words, when B
is low, the count increments on the rising edge of input A and decrements on the
falling edge of input A. If B is high, all rising transitions on input A are ignored.
The counter changes value only on one edge of input A as shown in Figure 5.
For more information see
Direction Inhibit and Direction Invert Output
and their effect on Quadrature signals on
page 27
.
Table 5 - Up and Down Counting
Direction
Inhibit Bit
Direction
Invert Bit
Input A (count)
Input B (direction)
Change in
Count Value
0
0
0, 1,
1
0, 1,
-1
0
0
1
0, 1,
-1
0, 1,
1
0
1
0
0, 1,
1
0, 1,
1
0
1
1
0, 1,
-1
0, 1,
-1
0
TIP
When both A and B transition at the same time, instead of in the defined
90° phase separation, the quadrature signal is invalid.