Module Operation

This chapter details the operation of the 1769-HSC module. We strongly suggest
that you review this information before configuring your module.

Counter Defaults

When the module powers up, all output array and configuration array values are
set to their default values. Refer to

Chapter 4 on page 65

or

Appendix D on page

149

for default values. All input array values are cleared. None of the module data

is retentive through a power cycle.

Power cycling the module has the following effects:

Clears stored counts and configurations
Clears faults and flags
Turns outputs off