Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

23

Module Operation

Chapter 2

See

Direction Inhibit and Direction Invert Output Control Bits on page 21

for

more information.

Pulse/Internal Direction Mode Selection

When the Pulse/Internal Direction mode is selected, the status of the Direction
Invert bit, as controlled by the user program, determines the direction of the
counter. The counter increments on the rising edge of the module’s A input
when the Direction Invert bit is reset (0). The counter decrements on the rising
edge of the A input when the Direction Invert bit is set (1).

Table 2 - Pulse External Direction Counting

Direction
Inhibit Bit

Direction
Invert Bit

Input A (count)

Input B (direction) Change in

Count Value

0

0

0 or open

1

1

-1

0, 1,

Don’t care

0

0

1

0 or open

-1

1

1

0, 1,

Don’t care

0

1

0

0 or open

1

1

1

0, 1,

Don’t care

0

1

1

0 or open

-1

1

-1

0, 1,

Don’t care

0

Table 3 - Pulse Internal Direction Counting - Counters 0 and 1

Direction
Inhibit Bit

Direction
Invert Bit

Input A (count)

Input B

Change in Count
Value

Don’t care

0

Don’t care

1

0, 1,

Don’t care

0

Don’t care

1

Don’t care

-1

0, 1,

Don’t care

0

Table 4 - Pulse Internal Direction Counting - Counters 2 and 3

Direction
Inhibit Bit

Direction
Invert Bit

Input A

Input B (count)

Change in Count
Value

Don’t care

0

Don’t care

1

Don’t care

0, 1,

0

Don’t care

1

Don’t care

-1

Don’t care

0, 1,

0