Temperature derating – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 128

Advertising
background image

128

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

Appendix A

Specifications

Temperature Derating

Refer to the following figures for 1769-HSC temperature derating.

Figure 22 - Maximum Input Voltage - 24V DC Operation

Figure 23 - Maximum Output Voltage - 24V DC Operation

(-32)

(50)

(68)

(86)

(104)

(122)

(140)

(158)

Voltage Derating Based on Temperature

Ambient Temperature, °C (°F))

Volts

(DC)

26.4V DC at
55 °C (131 °F)

45204

Temperature

Derated Voltage

(1)

(1) Input voltage derating between 55…60 °C is achieved by using a dropping resistor.

For 24V DC input voltage, use a 2.4 k

, ½ W resistor.

For input voltages greater than 24V DC, use a ½ W resistor with value: 125 x (V

in

- 5V).

0…40 °C (-32…104 °F)

30V DC

55 °C (131 °F)

26.4V DC

60 °C (140 °F)

5V DC

(-32)

(50)

(68)

(86)

(104)

(122)

(140)

(158)

Voltage Derating Based on Temperature

Ambient Temperature, °C (°F)

Volts

(DC)

26.4V DC at
55 °C (131 °F)

45205

Temperature

Derated Voltage

0…40 °C (-32…104 °F)

30V DC

55…60 °C (131…140 °F)

26.4V DC

Advertising