Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

Chapter 4

Module Configuration, Output, and Input Data

Output Array

The output array, which consists of 34 words, lets you access the module’s real-
time output data to control the module. The default value is all zeros.

IMPORTANT

The output array contains dynamic configuration data. The settings in the
output array must be compatible with the settings in the configuration
array.

For example, do not attempt to set Counter Control Bits for a given
counter in the output array unless NumberOfCounters in the
configuration array indicates that the counter is declared to be used.

IMPORTANT

All Not used bits (shaded in the

Output Array - 1769-HSC Module and

CMX 5370 L2 Packaged Controller Embedded HSC

table, below) must be

set to 0 or the InvalidOutput bit in the input array will be set. When the
InvalidOutput bit is set, the entire output array is rejected until an output
array that does not have this error is sent.

Table 14 - Output Array - 1769-HSC Module and CMX 5370 L2 Packaged Controller Embedded HSC

Word

Bit

Function

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

Out
15

Out
14

Out
13

Out
12

Out
11

Out
10

Out
9

Out
8

Out
7

Out
6

Out
5

Out
4

Out
3

Out
2

Out
1

Out
0

Output On Mask

1

Out
15

Out
14

Out
13

Out
12

Out
11

Out
10

Out
9

Out
8

Out
7

Out
6

Out
5

Out
4

Out
3

Out
2

Out
1

Out
0

Output Off Mask

2

R15

R14

R13

R12

R11

R10

R9

R8

R7

R6

R5

R4

R3

R2

R1

R0

Range Enable

3

Not used

Not used

4

Not used

RBF

Not used

Reset Blown Fuse

5

Not used

RP
W

RRE
Z

Z Inh Z Inv D

Inh

D
Inv

RU

RO

SP

En

Counter 0 Control Bits

6

Not used

RP
W

RRE
Z

Z Inh Z Inv D

Inh

D
Inv

RU

RO

SP

En

Counter 1 Control Bits

7

Not used

RP
W

Not used

D
Inv

RU

RO

SP

En

Counter 2 Control Bits

8

Not used

RP
W

Not used

D
Inv

RU

RO

SP

En

Counter 3 Control Bits

9

Not used

Not used

10

Range12To15[0].HiLimOrDirWr

Range High Limit or
Direct Write Value

11

12

Range12To15[0].LowLimit

Range Low Limit

13

14

Range12To15[0].OutputControl

Range Output Control

15

Not used

Inv

Not used

LD
W

Type

Not used

ToThisCtr

Range Configuration
Flags

16

Range12To15[1].HiLimOrDirWr

Range High Limit or
Direct Write Value

17

18

Range12To15[1].LowLimit

Range Low Limit