Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

81

Module Configuration, Output, and Input Data

Chapter 4

Cyclic Rate Update Time (CtrnCyclicRateUpdateTime)

This value is used to set the cyclic rate update time for the CurrentRate
calculation. The value indicates the time in milliseconds from 1…32767. An
invalid number causes a configuration error. The default value is 10 for counters 0
and 1. The default value is 0 for counters 2 and 3.

See

Cyclic Rate Calculation Method (current rate) on page 32

for more

information on cyclic rate.

IMPORTANT

Do not change this value while the counter is enabled. Attempting to do
so will result in a BadModConfigUpdate error. See

page 120

for a list

of prohibited settings.

IMPORTANT

The Counter Scalar information does not apply to the L23E packaged
controller because rate measurement is not supported.

Configuration Array Words

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

14

Counter 0 Cyclic Rate Update Time

Ctr0CyclicRateUpdateTime

24

Counter 1 Cyclic Rate Update Time

Ctr1CyclicRateUpdateTime

34

Counter 2 Cyclic Rate Update Time

Ctr2CyclicRateUpdateTime

44

Counter 3 Cyclic Rate Update Time

Ctr3CyclicRateUpdateTime

IMPORTANT

Do not change this value while the counter is enabled. Attempting to do
so will result in a BadModConfigUpdate error. See

page 120

for a list of

prohibited settings.