82

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

Chapter 4

Module Configuration, Output, and Input Data

Configuration Flags

Operational Mode (Ctr

n

Config.OperationalMode_0 through

Ctr

n

Config.OperationalMode_2)

These bits apply to Counters 0 and 1 only.

This value determines how the A

0 or A1 and B0 or B1 inputs are decoded when

assigned to counter 0 or counter 1.

Configuration Array Words

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

15 Counter 0 Configuration Flags

Not used

Linear

Not
used

Storage mode

Not used

Operational mode

25 Counter 1 Configuration Flags

Not used

Linear

Not
used

Storage mode

Not used

Operational mode

35 Counter 2 Configuration Flags

Not used

Linear

Not used

45 Counter 3 Configuration Flags

Not used

Linear

Not used

Set bit

For function

CtrnConfig.OperationalMode_2

CtrnConfig.OperationalMode_1

CtrnConfig.OperationalMode_0

0

0

0

Pulse internal direction

0

0

1

Pulse external direction

1

0

0

Quadrature encoder X1

1

0

1

Quadrature encoder X2

1

1

0

Quadrature encoder X4

0

1

0

Up/Down Pulses

0

1

1

reserved

1

1

1

reserved

TIP

The Ctr1Config.OperationalMode bits are reserved if the Number of
Counters equals 1. Attempting to set reserved bits will result in a
configuration error.

IMPORTANT

Do not change this value while the counter is enabled. Attempting to do
so will result in a BadModConfigUpdate error. See

page 120

for a list of

prohibited settings.