Input Frequency

Maximum input frequency is determined by the input configuration as shown in
the table.

Counter Types

Each of the four possible counters can be configured to stop counting and set a
flag at its limits (linear counter) or to rollover and set a flag at its limits (ring
counter). A counter’s limits are programmed by the Ctr

nMaxCount and

Ctr

nMinCount words in the module’s configuration array. Both types are

described below.

Linear Counter

Figure 7 illustrates linear counter operation. In linear operation, the current count
(Ctr[

n].CurrentCount) value remains between, or equal to, the

user-programmed minimum count (Ctr

nMinCount) and maximum count

(Ctr

nMaxCount) values. If the Ctr[n].CurrentCount value goes above (>) or

below (<) these values, the counter stops counting, and an overflow/underflow
bit is set. The overflow/underflow bits can be reset using the
Ctr

nResetCounterOverflow and CtrnResetCounterUnderflow bits.

Figure 7 - Linear Counter Diagram

Pulses are not accumulated in an overflow/underflow state. The counter begins
counting again when pulses are applied in the proper direction. For example, if
you exceed the maximum by 1000 counts, you do not need to apply 1000 counts
in the opposite direction before the counter begins counting down. The first
pulse in the opposite direction decrements the counter.

Input Configuration

Input Frequency
1769-HSC Module

Input Frequency
Packaged Controller

X4 Quadrature encoder

250 kHz

250 kHz

X2 Quadrature encoder

500 kHz

250 kHz

All other configurations

1 MHz

250 kHz

Count Up

Count Down

Counter Value

Maximum Count Value

Overflow and Hold

Minimum Count Value

Underflow and Hold

0