Wire diagrams, Inputs – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 59

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

59

Installation and Wiring

Chapter 3

Wire Diagrams

The following pages show wiring examples for a differential encoder,
single-ended encoder, and discrete device.

Inputs

The module utilizes differential inputs. Therefore, two input terminals are
required for each input point. For example, the A0+ and A0- terminals are
required for input point A0. Each input point is isolated from other input points,
the 1769 Compact bus, and the entire output terminal group.

The inputs are compatible with standard differential line driver output devices as
well as single-ended devices such as limit switches, photo-eyes, and proximity
sensors. Examples of differential and single-ended circuits are shown in

Figure 14

and

Figure 15

.

Figure 14 - Differential Encoder Wiring

(1)

Refer to your encoder manual for proper cable type. The type of cable used should be twisted pair, individually
shielded cable with a maximum length of 300 m (1000 ft).

A

A

B

B

Z

Z

A1(+)

A1(–)

B1(+)

B1(–)

Z1(+)

Z1(–)

GND

VS

+VDC

COM

Cable

(1)

Power
Supply

Allen-Bradley
845H Series
Differential
Encoder

Shield/Housing
Connect only if housing is electronically
isolated from the motor and ground.

Shield

Module Inputs

Earth

Advertising