Number of counters, Summary of available counter configurations – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 18

18
Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
Chapter 2
Module Operation
Number of Counters
The module has six input points: A0, B0, Z0, A1, B1, and Z1. Through these
inputs, the module can function with 1, 2, 3, or 4 counters depending upon the
number of counters and the operational mode configuration of the input points.
Summary of Available
Counter Configurations
The table summarizes the input configurations available for all counters, based on
the number of counters.
No. of Counters
Counter
Operational Mode
Gate or Preset Functionality
1 Counter
0
Any
All
1 through 3
Not available
2 Counters
0
Any
All
1
Any
All
2 and 3
Not available
3 Counters
0
Any
All
1
Pulse/Internal Direction
All
2
Pulse/Internal Direction
None
3
Not available
4 Counters
0
Pulse/Internal Direction
All
1
Pulse/Internal Direction
All
2
Pulse/Internal Direction
None
3
Pulse/Internal Direction
None