Number of counters, Summary of available counter configurations – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 18

Advertising
background image

18

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

Chapter 2

Module Operation

Number of Counters

The module has six input points: A0, B0, Z0, A1, B1, and Z1. Through these
inputs, the module can function with 1, 2, 3, or 4 counters depending upon the
number of counters and the operational mode configuration of the input points.

Summary of Available
Counter Configurations

The table summarizes the input configurations available for all counters, based on
the number of counters.

No. of Counters

Counter

Operational Mode

Gate or Preset Functionality

1 Counter

0

Any

All

1 through 3

Not available

2 Counters

0

Any

All

1

Any

All

2 and 3

Not available

3 Counters

0

Any

All

1

Pulse/Internal Direction

All

2

Pulse/Internal Direction

None

3

Not available

4 Counters

0

Pulse/Internal Direction

All

1

Pulse/Internal Direction

All

2

Pulse/Internal Direction

None

3

Pulse/Internal Direction

None