Configuration errors – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 115

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

115

Diagnostics and Troubleshooting

Chapter 5

Configuration Errors

If you set the fields in the configuration file to invalid or unsupported values, the
module ignores the invalid configuration, generates a non-critical error, and keeps
operating with the previous configuration.

The

Configuration Error Codes table on page 117

lists the possible

module-specific configuration error codes defined for the module. Correct the
error by providing proper configuration data to the module.

Table 21

describes configuration errors in more general terms.

Table 21 - Error Conditions by Type of Configuration

Programming Words

Error Conditions

General Configuration Bits,
Filters and Safe State Words

Unused or Reserved bit were set.
A counter or counters were running when the general

configuration bits or filter and safe state words were sent.

Counter Configuration

Unused or Reserved bit were set.
Operational Mode is invalid for the counter. (NumberOfCounters

may be incorrect.)

Operational Mode is invalid for the counter. (mode selection

may be incorrect).

The selected counter was running when the configuration was

sent.

CtrnMaxCount

 CtrnMinCount

CtrnHysteresis < 0

(1)

CtrnScalar < 1

(1)

CtrnCyclicRateUpdateTime < 1

(1)

The preset value is outside its valid range. (CtrnPreset not equal

to or between CtrnMinCount or CtrnMaxCount)

Counter was running when the minimum/maximum count value

was changed.

(1) Does not apply to the packaged controller.

Range Configuration

Unused or Reserved bit were set.
Range0to11[n].HighLimit

 Range0to11[n].LowLimit

(1)

Range0To11[n].ToThisCounter refers to a non-declared counter

(Range0To11[n].ToThisCounter > NumberOfCounters)

(1)

Advertising