Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 61

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

61

Installation and Wiring

Chapter 3

Figure 16 - Discrete Device Wiring

(1)

External resistors are required if they are not internal to the sensor. The pull-up resistor (R) value depends on
the power supply value. The table below shows the maximum resistor values for typical supply voltages. To
calculate the maximum resistor value, use the following formula:

where:
R = maximum pull-up resistor value
VDC = power supply voltage
Vmin = 2.6V DC
Imin = 6.8 mA

The minimum resistor (R) value depends on the current sinking capability of the
sensor. Refer to your sensor’s documentation.

Power Supply Voltage (V DC)

Pull-up Resistor Value (R), Max

(1)

(1) Resistance values can change, depending upon your application.

5

352

12

1382

24

3147

VS

A1(+)

A1(–)

B1(+)

B1(–)

Z1(+)

Z1(–)

+VDC

COM

VS

OUT

COM

OUT

COM

VS

OUT

COM

R

(1)

Power
Supply

Module Inputs

Solid-state
Switch

Proximity Sensor

Photo-electric Sensor
with Open Collector
Sinking Output

R

VDC Vmin

Imin

--------------------------------------------

=

Advertising