Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 125

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

125

Specifications

Appendix A

Table 28 - Environmental Specifications - 1769-HSC

Attribute

1769-HSC

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

0…60 °C (32…140 °F)

Temperature, surrounding air, max
For UL certified open equipment

40 °C (104 °F)

Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackahed Nonoperating Cold),
IEC 60068-2-2 (TestBb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity
IEC 60068-2-3e0 (Test Db, Unpackaged Damp Heat)

5...95% noncondensing

Vibration, operating
IEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz, peak-to-peak

Vibration, relay operation

2 g @ 10…500 Hz

(1)

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g, 11 ms panel mounted
20 g, 11 ms DIN rail mounted

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

40 g, panel mounted
30 g, DIN rail mounted

Emissions
CISPR 11

Group 1, Class A

ESD immunity
IEC 61000-4-2

6 kV contact discharges
8 kV air discharges

Radiated RF immunity
IEC 6100-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 and 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity
IEC 61000-4-4

±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports

Surge transient immunity
IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
±1 kV line-earth (CM) on shielded ports

Conducted RF immunity
IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

(1) This rating applies for your system if a relay module, such as the 1769-OW8, is used.