Input array – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 98

Advertising
background image

98

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

Chapter 4

Module Configuration, Output, and Input Data

Inv - Range Invert (Range12To15[

n

].Invert)

Indicates the active portion of Range

n. When Range12To15[n].Invert = 0, the

outputs are activated when the range value is at or between the
Range12To15[

n].LowLimit and Range12To15[n].HiLimOrDirWr. When

Range12To15[

n].Invert = 1, the outputs are activated when the range is at or

outside the range limits.

Input Array

The input array, which consists of 35 words, allows read-only access to the
module’s input data via word and bit access. The input array is described below.
The functions are described in more detail in the sections following the table.

Object Value (Current Count or Current Rate)

Low Limit

High Limit or
Direct Write Value

INACTIVE

ACTIVE

INACTIVE

ACTIVE

ACTIVE

INACTIVE

Invert Bit = 0

Invert Bit = 1

IMPORTANT

During the non-run states (program and fault), the module continues to
update the input array (continues counting). Depending on the bus
master, you may not see this.

TIP

Status bits for a particular counter reflect the configuration settings for
that counter. To receive valid status, the counter must be enabled and the
module must have stored a valid configuration for that counter.

Table 16 - Input Array - 1769-HSC Module and CMX 5370 L2 Packaged Controller Embedded HSC

Word

Bit

Function

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

0

Not used

Z1

B1

A1

Z0

B0

A0

Input State

1

Readback.0 through Readback.15

Readback

2

InvalidRangeLimit1
2 through
InvalidRangeLimit1
5

InvalidCtrAssignToRange1
2 through
InvalidCtrAssignToRange1
5

Gen
Error

Invalid
Output

Mod
Config

Not used

Out0Overcurrent through
Out3Overcurrent

Status Flags

3

RangeActive.0 through RangeActive.15

Range Active

4

Ctr[0].CurrentCount

Counter 0 Current
Count

5

6

Ctr[0].StoredCount

Counter 0 Stored
Count

7