Status Indicators

The front panel of the 1769-HSC module has a total of 12 status indicators.

For information about the packaged controllers’ status indicators, see the
CompactLogix Packaged Controllers Quick Start and User Manual,
publication

IASIMP-QS010

.

Table 1 - Diagnostic Indicators

Indicator

Status

Description

0 OUT

Amber

ON/OFF logic status of output 0

1 OUT

Amber

ON/OFF logic status of output 1

2 OUT

Amber

ON/OFF logic status of output 2

3 OUT

Amber

ON/OFF logic status of output 3

FUSE

Red

Overcurrent

OK

Off

No power is applied

Red (briefly)

Performing self-test

Solid green

OK, normal operating condition

Flashing green

OK, module in Program or Fault mode

Solid red or amber

Hardware error. Cycle power to the module. If problem persists,
replace the module.

Flashing red

Recoverable fault. Reconfigure, reset, or perform error recovery.
See

Non-critical versus Critical Module Errors on page 113

. The

OK indicator flashes red for all of the error codes in the

Configuration Error Codes table on page 117

.

A0

Amber

ON/OFF status of input A0

A1

Amber

ON/OFF status of input A1

B0

Amber

ON/OFF status of input B0

B1

Amber

ON/OFF status of input B1

Z0

Amber

ON/OFF status of input Z0

Z1

Amber

ON/OFF status of input Z1

ALL ON

Possible causes for all status indicators to be On include the following:
Bus error has occurred—controller hard fault. Cycle power.
During load upgrade of controller—normal operation. Do not cycle power during the

load upgrade.

All indicators flash on briefly during powerup—normal operation.

45272

IN

OUT

0

2

FUSE

1

3

OK

AO

BO

ZO

A1

B1

Z1