117

Diagnostics and Troubleshooting

Chapter 5

TIP

The OK status indicator flashes red for all error codes in the

Configuration Error Codes

table.

IMPORTANT

Only error codes X400…X443 apply to the packaged controller.

Table 23 - Configuration Error Codes

Hex
Equivalent

(1)

Module
Error
Code

Extended
Error
Information
Code

Error

Description

Binary

Binary

X400

010

0 0000 0000

General Configuration Error

No additional information

X401

010

0 0000 0001

UnusedConfigBitSet

One or more of the unused module configuration bits are set.

X402

010

0 0000 0010

BadModConfigUpdate

Occurs when you attempt to change a forbidden module
configuration parameter while a counter or range is still enabled.
See

Table 24

on

page 120

for a list of the forbidden parameters.

X411

010

0 0001 0001

BadCounterNum_1

Nonzero configuration values were entered for Counter 1, when
Counter 1 was not available.

X412

010

0 0001 0010

BadCounterNum_2

Nonzero configuration values were entered for Counter 2, when
Counter 2 was not available.

X413

010

0 0001 0011

BadCounterNum_3

Nonzero configuration values were entered for Counter 3, when
Counter 3 was not available.

X420

010

0 0010 0000

BadCounterMode_0

Operation Mode_0 is set to an invalid value. For example, value is
reserved (011 or 111) or nonzero when NumberofCounters = 11.

X421

010

0 0010 0001

BadCounterMode_1

Operation Mode_1 is set to an invalid value. For example, value is
reserved (011 or 111) or nonzero when NumberofCounters = 10 or
11.

X430

010

0 0011 0000

BadMin_0

Programmed Ctr0MinCount is greater than the Ctr0MaxCount.

X431

010

0 0011 0001

BadMin_1

Programmed Ctr1MinCount is greater than the Ctr1MinCount.

X432

010

0 0011 0010

BadMin_2

Programmed Ctr2MinCount is greater than the Ctr2MaxCount.

X433

010

0 0011 0011

BadMin_3

Programmed Ctr3MinCount is greater than the Ctr3MaxCount.

X440

010

0 0100 0000

BadPreset_0

The programmed Ctr0Preset is greater than the Ctr0MaxCount or
less than the Ctr0MinCount.

X441

010

0 0100 0001

BadPreset_1

The programmed Ctr1Preset is greater than the Ctr1MaxCount or
less than the Ctr1MinCount.

X442

010

0 0100 0010

BadPreset_2

The programmed Ctr2Preset is greater than the Ctr2MaxCount or
less than the Ctr2MinCount.

X443

010

0 0100 0011

BadPreset_3

The programmed Ctr3Preset is greater than the Ctr3MaxCount or
less than the Ctr3MinCount.

X450

010

0 0101 0000

BadHysteresis_0

The Ctr0Hysteresis value is invalid, that is, less than zero.

X451

010

0 0101 0001

BadHysteresis_1

The Ctr1Hysteresis value is invalid, that is, less than zero.

X452

010

0 0101 0010

BadHysteresis_2

The Ctr2Hysteresis value is invalid, that is, less than zero.

X453

010

0 0101 0011

BadHysteresis_3

The Ctr3Hysteresis value is invalid, that is, less than zero.

X460

010

0 0110 0000

BadScalar_0

The Ctr0Scalar value is invalid, that is, less than one.

X461

010

0 0110 0001

BadScalar_1

The Ctr1Scalar value is invalid, that is, less than one when
NumberofCounters = 01, 10 or 11.