Error Codes

The tables in this section explain the extended error codes for general common
hardware errors, configuration errors, and runtime errors.

Table 22 - General Common Hardware Error Codes

Error Type

Hex
Equivalent

(1)

Module
Error Code

Extended Error
Information
Code

Description

Status of the
OK Indicator

(2)

Binary

Binary

No Error

X000

000

0 0000 0000

OK, normal operating condition.

Solid or flashing green

General Common
Hardware Error

X200

001

0 0000 0000

General hardware error; no additional
information

Solid red

X201

001

0 0000 0001

Power-up reset state

Briefly red

X202

001

0 0000 0010

Bus master incompatibility

Solid red

X203

001

0 0000 0011

General hardware error

Solid red

X210

001

0 0000 1010

General microprocessor error

Solid red

X211

001

0 0000 1011

Microprocessor internal register error

Solid red

X212

001

0 0000 1100

Microprocessor special function register error

Solid red

X213

001

0 0000 1101

Microprocessor internal memory error

Solid red

X214

001

0 0000 1110

Microprocessor timer error

Solid red

X215

001

0 0000 1111

Microprocessor interrupt error

Solid red

X216

001

0 0001 0000

Microprocessor watchdog error

Solid red

X220

001

0 0001 1000

Firmware corrupt

Solid red

X221

001

0 0001 1001

Firmware checksum error in non-volatile RAM

Solid red

X222

001

0 0001 1010

Firmware checksum error in RAM

Solid red

X230

001

0 0001 1110

External RAM test error

Solid red

X231

001

0 0001 1111

External RAM cell test error

Solid red

X240

001

0 0010 0100

Gate array loading failed

Solid red

X250

001

0 0011 0010

External watchdog error

Solid red

(1) X represents the ‘Don’t Care’ digit.