Rate range – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual
Page 39

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013
39
Module Operation
Chapter 2
Rate Range
In a non-inverted rate range, the outputs are active if the rate measurement is
within the user-defined range. In an inverted rate range, the outputs are active if
the rate measurement is outside the user-defined range. The input rate can be up
to 1 MHz in either direction.
Figure 10 shows all ranges referring to one counter. The module is capable of
individually assigning each range to any counter. Each counter can also have a
combination of count and rate ranges.
Figure 10 - Rate Range Example
IMPORTANT
The Rate Range information does not apply to the packaged controller.
-1,000,000
1,000,000
0
Ctr[0].CurrentRate
Range 4
Range 1
Range 2
Range 4
Output 0
Output 1
Output 2
Output 3
On
Off
Range 3
Table 10 - Rate Range Example Values
Range
Range
Counter
Number
Range
Type
(1)
Range
Low
Limit
Range
High
Limit
Range
Invert
Bit
Outputs
(2)
(Range[n].OutputControl word)
Outputs
Affected
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
1
00
1
-7000
-5000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
2
00
1
-1000
4500
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
3
00
1
-4000
3000
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
2
4
00
1
-20,000
20,000
1
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
1
0 and 3
(1) For Range Type, 0 = count range and 1 = rate range.
(2) Bits 0…3 are real outputs. Bits 4…15 are virtual outputs.