Operational mode selection – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 21

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

21

Module Operation

Chapter 2

Operational Mode
Selection

A count channel’s operational mode configuration selection determines how the
A and B inputs cause a counter channel to increment or decrement. The six
available mode selections are the following:

Pulse/External Direction Input
Pulse/Internal Direction Input
Up and Down Pulse Input
X1 Quadrature Encoder Input
X2 Quadrature Encoder Input
X4 Quadrature Encoder Input

See

Figure 2 on page 19

for the operational modes available for the counters,

based on the number of counters configured.

Direction Inhibit and Direction Invert Output Control Bits

These bits apply to all of the counter modes.

IMPORTANT

The operational mode selection is limited by the number of counters
selected.

With two counters selected, Counters 0 and 1 can be assigned any
operational mode.

With three counters selected, Counter 0 can be assigned any mode,
but Counters 1 and 2 can only be configured as pulse/internal
direction.

With four counters selected, all counters must be configured for the
pulse/internal direction mode.

TIP

When set, the Direction Inhibit bit disables any physical input from
affecting count direction.

When set, the Direction Invert bit changes the direction of the counter in
all operational modes.

When Direction Inhibit is set, then Direction Invert is the direction.