Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 153

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

153

Programming Quick Reference

Appendix D

The default value for the output array is all zeroes.

Table 32 - Output Array for the 1769-HSC Module

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Description

0

Out15

Out14

Out13

Out12

Out11

Out10

Out09

Out08

Out07

Out06

Out05

Out04

Out03

Out02

Out01

Out00 OutputOnMask.0 -- OutputOnMask.15

1

Out15

Out14

Out13

Out12

Out11

Out10

Out09

Out08

Out07

Out06

Out05

Out04

Out03

Out02

Out01

Out00 OutputOffMask.0 -- OutputOffMask.15

2

R15

R14

R13

R12

R11

R10

R09

R08

R07

R06

R05

R04

R03

R02

R01

R00

RangeEn.0 -- RangeEn.15

3

Reserved

4

RBF

ResetBlownFuse

5

RPW

RREZ

Z Inh

Z Inv

D Inh

D Inv

RCU

RCO

SP

En

Ctr0ControlBits

 Ctr0En

Ctr0SoftPreset
Ctr0ResetCountOverflow
Ctr0ResetCountUnderflow
Ctr0DirectionInvert
Ctr0DirectionInhibit
Ctr0ZInvert
Ctr0ZInhibit
Ctr0ResetRisingEdgeZ
Ctr0ResetCtrPresetWarning

6

RPW

RREZ

Z Inh

Z Inv

D Inh

D Inv

RCU

RCO

SP

En

Ctr1ControlBits

7

RPW

D Inv

RCU

RCO

SP

En

Ctr2ControlBits

8

RPW

D Inv

RCU

RCO

SP

En

Ctr3ControlBits

9

Reserved

10
11

Range12To15[0].HiLimOrDirWr

Range12To15[0].HiLimOrDirWr

12
13

Range12To15[0].LowLimit

Range12To15[0].LowLimit

14

Out15

Out14

Out13

Out12

Out11

Out10

Out09

Out08

Out07

Out06

Out05

Out04

Out03

Out02

Out01

Out00 Range12To15[0].OutputControl.0 ... .15

15

Inv

LDW

Type

ToThisCtr

Range12To15[0].Config Flags

 Range12To15[0].ToThisCounter_0

Range12To15[0].ToThisCounter_1
Range12To15[0].Type
Range12To15[0].LoadDirectWrite
Range12To15[0].Invert

16
17

Range12To15[1].HiLimOrDirWr

Range12To15[1].HiLimOrDirWr

18
19

Range12To15[1].LowLimit

Range12To15[1].LowLimit

20

Out15

Out14

Out13

Out12

Out11

Out10

Out09

Out08

Out07

Out06

Out05

Out04

Out03

Out02

Out01

Out00 Range12To15[1].OutputControl.0 ... .15

21

Inv

LDW

Type

ToThisCtr

Range12To15[1].Config Flags

 Range12To15[1].ToThisCounter_0

Range12To15[1].ToThisCounter_1
Range12To15[1].Type
Range12To15[1].LoadDirectWrite
Range12To15[1].Invert

22
23

Range12To15[2].HiLimOrDirWr

Range12To15[2].HiLimOrDirWr

24
25

Range12To15[2].LowLimit

Range12To15[2].LowLimit

26

Out15

Out14

Out13

Out12

Out11

Out10

Out09

Out08

Out07

Out06

Out05

Out04

Out03

Out02

Out01

Out00 Range12To15[2].OutputControl.0 ... .15

27

Inv

LDW

Type

ToThisCtr

Range12To15[2].Config Flags

 Range12To15[2].ToThisCounter_0

Range12To15[2].ToThisCounter_1
Range12To15[2].Type
Range12To15[2].LoadDirectWrite
Range12To15[2].Invert

28
29

Range12To15[3].HiLimOrDirWr

Range12To15[3].HiLimOrDirWr

30
31

Range12To15[3].LowLimit

Range12To15[3].LowLimit

32

Out15

Out14

Out13

Out12

Out11

Out10

Out09

Out08

Out07

Out06

Out05

Out04

Out03

Out02

Out01

Out00 Range12To15[3].OutputControl.0 ... .15

33

Inv

LDW

Type

ToThisCtr

Range12To15[3].Config Flags

 Range12To15[3].ToThisCounter_0

Range12To15[3].ToThisCounter_1
Range12To15[3].Type
Range12To15[3].LoadDirectWrite
Range12To15[3].Invert

Advertising