Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

45

Chapter

3

Installation and Wiring

This chapter explains how to install and wire the 1769-HSC module.

Topic

Page

Power Requirements

47

General Considerations

47

System Assembly

49

Mount the Module

50

Replace the Module within a System

53

Field Wiring Connections

54

IMPORTANT

For information about installing and wiring the packaged controllers,
refer to the CompactLogix Packaged Controller Installation Instructions,
publication

1769-IN082

.

ATTENTION: Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate
precautions, there can be difficulties with electromagnetic compatibility in residential and other environments due to
conducted and radiated disturbances.

This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed
for those specific environmental conditions that will be present and appropriately designed to prevent personal injury
resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or
minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic.
The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may
contain additional information regarding specific enclosure type ratings that are required to comply with certain
product safety certifications.

In addition to this publication, see the following:

Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

, for additional installation

requirements

NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by
enclosures