Output Fault Value (Out0FaultValue through Out3FaultValue)
These bits are the values that will be applied to each of the real outputs when
User-defined Safe State is set as described and the module is in Fault state.
Counter Maximum Count (CtrnMaxCount)
This is the maximum count value allowed for counter (
n). The count value
cannot exceed this value. Allowable values are Ctr
nMinCount 1…2,147,483,647
(decimal).
The default value is 2,147,483,647 decimal for counters 0 and 1. The default
value is 0 for counters 2 and 3.
Configuration Array Word 5
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
5
Output Fault Value
Not used
Out3
FV
Out2
FV
Out1
FV
Out0
FV
TIP
Outputs are also affected by PFT above.
Configuration Array Words
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
6
Counter 0 Maximum
Count
Ctr0MaxCount
7
16
Counter 1 Maximum
Count
Ctr1MaxCount
17
26
Counter 2 Maximum
Count
Ctr2MaxCount
27
36
Counter 3 Maximum
Count
Ctr3MaxCount
37
IMPORTANT
Do not change this value while the counter is enabled. Attempting to do
so will result in a BadModConfigUpdate error. See
for a list
of prohibited settings.