Replace the module within a system, Replace the module within a – Rockwell Automation 1769-HSC Compact High Speed Counter Module User Manual

Page 53

Advertising
background image

Rockwell Automation Publication 1769-UM006E-EN-P - July 2013

53

Installation and Wiring

Chapter 3

Replace the Module within
a System

The module can be replaced while the system is mounted to a panel or DIN rail.

1. Remove power, referring to the Warning on

page 47

.

2. Remove terminal block or disconnect input and/or output wiring from the

module.

3. Remove the upper and lower mounting screws from the module (or open

the DIN latches using a screwdriver).

4. On the module to be replaced and the right-side adjacent module (or end

cap if the module is the last module in the bank), move the bus levers to the
right (unlock) to disconnect the module from the adjacent modules.

5. Gently slide the disconnected module forward.

If you feel excessive resistance, make sure that you disconnected the
module from the bus and that you removed both mounting screws (or
opened the DIN latches).

6. Before installing the replacement module, be sure that the bus lever on the

right-side adjacent module is in the unlocked (fully-right) position.

7. Slide the replacement module into the open slot.

8. Connect the modules together by locking (fully-left) the bus levers on the

replacement module and the right-side adjacent module or end cap.

9. Replace the mounting screws (or snap the module onto the DIN rail).

10. Replace the terminal block or connect the input and/or output wiring to

the module.

TIP

It may be necessary to rock the module slightly from front
to back to remove it, or, in a panel-mounted system, to
loosen the screws of adjacent modules.