Chapter 5 Diagnostics and Troubleshooting

The BadModConfigUpdate error conditions are shown in the following table.
They occur when you attempt to change a forbidden module configuration
parameter while a counter or range is still enabled. To recover from this situation,
do the following:

Correct the configuration problem.
Reconfigure the module.

TIP

Refer to your controller’s documentation for available reconfiguration
methods.

IMPORTANT

Do not change the module settings in

Table 24

while counter or range is

enabled.

Table 24 - ‘BadModConfigUpdate’ Error Prohibited Configuration Settings

Configuration Parameters

Array Position

Prohibited from changing when indicated bits (X) are set

Word

Bit

Ctr0EN

Ctr1EN

Ctr2EN

Ctr3EN

RangeEN

OverCurrentLatchOff

0

0

X

X

X

X

X

ProgToFaultEn

0

4

NumberOfCounters

0

8 and 9

X

X

X

X

X

Filter_A0

1

0 and 1

X

X

Filter_B0

1

3 and 4

X

X

Filter_Z0

1

6 and 7

X

X

Filter_A1

1

8 and 9

X

X

Filter_B1

1

11 and 12

X

X

Filter_Z1

1

14 and 15

X

X

OutnProgramMode

2

0 to 3

OutnProgramStateRun

2

4 to 7

OutnProgramValue

3

0 to 3

Outn0FaultMode

4

0 to 3

OutnFaultStateRun

4

4 to 7

OutnFaultValue

5

0 to 3

Ctr0MaxCount

Ctr0MinCount

Ctr0Preset

(1)

Ctr0Hysteresis

(2)

Ctr0Scalar

(2)

Ctr0CyclicRateUpdateTime

(2)

Ctyr0Config.OperationMode

Ctr0Config.StorageMode

Ctr0Config.Linear

6 and 7

8 and 9

10 and 11

12

13

14

15

15

15

--

--

--

--

--

--

0 to 3

8 to 10

12

X

X

(1)

X

X

X

X

X

X

Advertising