Chapter 7

Troubleshooting and Maintenance

7–16

Only available on the RS-485 Comm port version. Use the TXEN test to
verify the transmit enable line at the RS-485 communications port.

The TXEN test requires a loopback connector with an LED. You can
construct a simple loopback connector as shown below:

DB9 Female

1

Data Out -

2

Data Out +

3

Data In -

4

Data In +

5

Signal Ground

6

Transmit Enable

7

Not Used

8

Signal Ground

9

Shield

Pin Signal Name

RS-485 Comm Port Only

Connects pins 1

!3

and pins 2

! 4

LED and 750

W resistor

between pins 2-4 and 6

Loopback Connector

750

W

LED

To test the transmit enable line:

1. Use the [NEXT] or [PREV] keys to display TXEN/ & Alarm Test on the

test selection screen.

DTAM Plus Diagnostic
NEXT to Select Test
ENTER To Initiate

TXEN/ & Alarm

2. Press [

] to initiate the test.

The following screen appears.

Toggling TXEN Line
A stable Alarm LED

Press ENTER

The Alarm LED flashes at approximately 1 second intervals indicating
that the transmit enable line is functioning properly.

3. Pressing [

] terminates the TXEN/ & Alarm test.

The next test selection screen is displayed.

DTAM Plus Diagnostic
NEXT to Select Test
ENTER To Initiate

Reset DUT

4. To terminate the test function , press the [NEXT] or [PREV] keys to

display Reset DUT in the test selection area. Press [

] to reset the

DTAM Plus.

TXEN Test