Rockwell Automation 2707-L40X_L8X_V40X DTAM Plus Operator Interface Module Installation Instructions User Manual

Page 80

Advertising
background image

Chapter 6

Communication Connections and Setup

6–4

DTAM Plus to DH-485 Network

SLC 5/01

Interface

Converter

Programming Terminal

Link Coupler

Link Coupler

Link Coupler

RS-232 to RS-485

DTAM Plus

Catalog No. 2707-V40P2

DH485 Network

Cable

(Catalog No. 2707-NC1)

Cable

(Catalog No. 2707-NC1)

DTAM Plus

(Multidrop)

RS-485

RS-485

To connect the DTAM Plus terminal to an RS-485 device:

1. Make sure that the power to the DTAM Plus is off.

2. Use the proper cabling to connect the DTAM Plus communications port

to the port of the controller (PLC-5 channel 0 or SLC 5/03 or SLC 5/04
RS-232 port).

Use cable, Catalog No. 2707-NC4 for PLC-5 channel 0 RS-422
connection

Use cable, Catalog No. 2707-NC5 for PLC-5 channel 0 RS-232
connection. The 2707-NC5 cable converts the signals from the
RS-485 port to RS-232 levels.

Use cable, Catalog No. 1747-CP3 for SLC 5/03, 5/04, 5/05 port
connection

If you need to make your own cable, refer to the connection diagrams
in Appendix B. The maximum cable length is 200 feet (60.8 meters).

Important: The DH-485 network cable requires proper shielding,
grounding, and termination. Refer to Data Highway / Data Highway Plus
/ Data Highway-485 Cable Installation Manual (Pub. No. 1770-6.2.2).

3. The DH-485 connectors are not electrically isolated. If electrical isolation

is required, use Link Couplers (Catalog No. 1747-AIC) shown above.

!

ATTENTION: Electrical isolation using Link Couplers (Catalog
No. 1747-AIC) is required in applications where the distance
between the DTAM Plus terminal and the SLC is greater than 6.5
feet (2 meters).

4. Make sure that the communication parameters of the DTAM Plus terminal

match the host device.

5. Apply power and verify that communications are established.

Advertising