Communication ports, Versions with comm port – Rockwell Automation 2707-L40X_L8X_V40X DTAM Plus Operator Interface Module Installation Instructions User Manual

Page 18

Advertising
background image

Chapter 1

DTAM Plus OverView

1–6

Versions with Comm Port

The configurable communications port of the DTAM Plus supports RS-485
or RS-232. Use RS-485 to communicate with SLC processors over the
Allen-Bradley DH485 network as:

one of 32 nodes on a multidrop network

direct connection to a single SLC processor or the 1746-BAS module.
Communication via the 1746-BAS module provides direct backplane
access and faster data throughput.

Use RS-232 to communicate point-to-point DF1 to Channel 0 of the PLC-5
processors. You can also use RS-232 to download/upload DTAM Plus
application programs or to use the DTAM Plus in Terminal mode.

Comm Port Only

Printer Port

RS-232 Connector

(9 Pin Male)

Comm Port

RS-485 / RS-232

Connector (9 Pin Female)

Comm Port

RS-485 / RS-232 Connector

(9 Pin Female)

Power Connector

Power Connector

Comm Port

with Printer Port

The DTAM Plus supports the following parameters for RS-485 and RS-232C
communications:

RS-485 and RS-232

Communications Parameters

Options

Baud Rate

300, 1200, 2400, 4800, 9600, 19200, 38400

Data Bits

7 or 8

Parity

Odd, Even, None

The DTAM Plus supports RS-422 with a PLC-5 (DF1 protocol) when the
Comm port is set to RS-485.

DF1 Communications Parameters

Options

Protocol

DF1 Full-Duplex

Error Detect

CRC

BAUD Rate

300, 1200, 2400, 4800, 9600, 19200 (Default-9600)

Parity

None or Even (Default = Even)

Control Line Operation

No Handshaking

Stop Bits

1

Communication Ports