Loading an Application

Chapter 2

2–7

It’s recommended that you use the RS-232 port for transferring applications.
On DTAM Plus versions with a Comm (RS-485 / RS-232) port, you can also
download applications using an RS-485 connection.

RS-485 / RS-232 Connector

(9 Pin Female)

Remote I/O Connector

(Terminal Block)

Power Connector

Remote I/O Version With

Comm Port

Versions with a Comm Port

Versions with a Comm Port

and Printer Port

Printer Port

RS-485 / RS-232 Connector

(9 Pin Female)

RS-485 / RS-232 Connector

(9 Pin Female)

Power Connector

Power Connector

To Computer
RS-485 Port or
Converter

Create your own cable

To download through the RS-485 port, you must:

set DIP switch position SW-2 ON

create a communication cable. The RS-485 port connections are:

DTAM Plus Comm Port

RS-485/RS-232 Connector

Pin 1 = TX485 -
Pin 2 = Tx485 +
Pin 3 = Rx485 -
Pin 4 = Rx485 +

Upload/download functions are initiated from a personal computer running
the programming software DPS (Catalog No. 2707-NP, series H or later).
Transfer functions always occur at 9600 Baud (regardless of the DTAM Plus
application’s printer or communications port settings).

After a reset with a valid application, the DTAM Plus baud rate is set to the
parameters defined by the application program residing in the DTAM Plus.

Upload / Download