Chapter 6

Communication Connections and Setup

6–10

SLC 5/03, 5/04, 5/05 (channel 0)

Make sure that the SLC DH-485 port is configured as follows:

Parameter

Selections

Recommended

Baud Rate

1200, 2400, 9600, 19.2K

19.2K

Node Address

0 to 31

Next lowest address on the
network. Set to 1 for point-to
point communications ①

.

Maximum Node
Address

0 to 31

Set to maximum node on net-
work. Set to 1 for point-to
point communications ①

.

Token Hold Factor

1 to 4

1

Diagnostic File Number

0 to 255

Any

Parity

None, Odd, or Even

Even②

Data Bits

7 or 8

8

For maximum response times on point-to-point networks, we recommend:
To transfer data quickly from the SLC 500 to the DTAM set as the SLC as node 0 and the DTAM as
node 1. Maximum node address should be 1.
To transfer data quickly from the DTAM to the SLC 500 set as the DTAM as node 0 and the SLC as
node 1. Maximum node address should be 1.

SLC 5/03, 5/04, 5/05 (channel 0) only supports EVEN parity.

The DTAM Plus must be set as follows for communication to occur. The
DTAM module uses DH485 protocol but the comm port is set for RS-232
(switch 1 position 2 is open).

Cable (Catalog No. 2707-NC2)

DTAM Plus

DH485

Cable (Catalog No.

1761-CBL-HM02)

RS-232

MicroLogix 1000

AIC+

RS-232

Cable (Catalog No. 2707-NC10)

DTAM Plus

Comm Port (RS-232)

MicroLogix 1000

RS-232

Comm Port (RS-232)

RS-232 Communications with
a MicroLogix 1000