Chapter 3

Using the Function Menu

3–4

The C-Port option on the Function Menu lets you manually adjust the
communication port parameters. Normally these parameters are set from the
DPS programming software when an application is downloaded.

Select C-Port [1] from the Function Menu.

1 C-Port

5 Special

2 P-Port

6 Term

3 Clk/Cal

7 Test

4 Reset

8 Other

This menu displays:

Select Item:
1 Baud Rate

4 Exit

2 Data Bits
3 Parity

Exits to Function Menu

Select an item by pressing the corresponding numeric key [1]

! [4].

Baud Rate

Selecting Baud Rate [1] displays the current baud rate.

Select Baud Rate:
Baud Rate

2400

”NEXT” To Change
”ENTER” To Select

Press [NEXT] to toggle through the options: 300, 1200, 2400, 4800, 9600,
19200, 38400. Press [

] to select a new rate. DH-485 communications

with an SLC or network cannot be set to 300 Baud.

Data Bits

Selecting Data Bits [2] displays the current setting.

Select Bit Counts:
Bits

8

”NEXT” To Change
”ENTER” To Select

Press [NEXT] to change between 7 or 8 bits. Press [

] to select a setting.

Parity

Selecting Parity [3] displays the current setting.

Select Parity:
Parity

None

”NEXT” To Change
”ENTER” To Select

Press [NEXT] to change between Even, Odd, or No parity. Press [

] to

select a new parity.

Setting Communication
Port Parameters